| 序号 | 增压稳压设备 型号
 | 消防压力 (Mpa)
 P1
 | 立式隔膜气压罐 | 配用水泵 | 设备运行 重量(Kg)
 | 运行压力 (Mpa)
 | 稳压水 容积(L)
 | 
| 型号规格 | 工作压力比 ab
 | 消防储水容积 | 
| 标定容积 | 实际容积 | 型号 | 
| 1 | ZW(L)-I-X-7 | 0.10 | SQL800×0.6 | 0.60 | 300 | 319 | 25LG3-10×4 N=1.5KW | 1452 | P1=0.10 PS1=0.26 P2=0.23 PS2=0.31
 | 54 | 
| 2 | ZW(L)-I-Z-10 | 0.16 | SQL800×0.6 | 0.80 | 150 | 159 | 25LG3-10×4 N=1.5kw | 1428 | P1=0.16 pS1=0.26 P2=0.23 pS2=0.31
 | 70 | 
| 3 | ZW(L)-I-X-10 | 0.16 | SQL800×0.6 | 0.60 | 300 | 319 | 25LG3-10×5 N=1.5KW | 1474 | P1=0.16 PS1=0.36 P2=0.33 PS2=0.42
 | 52 | 
| 4 | ZW(L)-I-X-13 | 0.22 | SQL1000×0.6 | 0.76 | 300 | 329 | 25lg3-10×4 N=1.5KW | 2312 | P1=0.22 PS1=0.35 P2=0.32 PS2=0.40
 | 97 | 
| 5 | ZW(L)-I-XZ-10 | 0.16 | SQL1000×0.6 | 0.65 | 450 | 480 | 25LG3-10×4 N=1.5KW | 2312 | P1=0.16 PS1=0.33 P2=0.30 PS2=0.38
 | 86 | 
| 6 | ZW(L)-I-XZ-13 | 0.22 | SQL1000×0.6 | 0.67 | 450 | 452 | 25LG3-10×5 N=1.5KW | 2312 | P1=0.22 PS1=0.41 P2=0.38 PS2=0.46
 | 80 | 
| 7 | ZW(L)-II-Z- | A | 0.22-0.38 | SQL800×0.6 | 0.80 | 150 | 159 | 25LG3-10×6 N=2.2kw | 1452 | P1=0.38 PS1=0.53 P2=0.50 PS2=0.60
 | 61 | 
| 8 | B | 0.38-0.50 | SQL800×1.0 | 0.80 | 150 | 159 | 25LG3-10×8 N=2.2kw | 1513 | P1=0.50 PS1=0.68 P2=0.65 PS2=0.75
 | 51 | 
| 9 | C | 0.50-0.65 | SQL1000×1.5 | 0.85 | 150 | 206 | 25LG3-10×9 N=2.2kw | 1653 | P1=0.65 PS1=0.81 P2=0.78 PS2=0.86
 | 59 | 
| 10 | D | 0.65-0.85 | SQL1000×1.5 | 0.85 | 150 | 206 | 25LG3-10×11 N=3.0kw | 1701 | P1=0.85 PS1=1.04 P2=1.02 PS2=1.10
 | 57 | 
| 11 | E | 0.85-1.00 | SQL1000×1.5 | 0.85 | 150 | 206 | 25LG3-10×13 N=4.0kw | 1709 | P1=1.00 PS1=1.21 P2=1.19 PS2=1.27
 | 50 | 
| 12 | ZW(L)-II-X- | A | 0.22-0.38 | SQL1000×0.6 | 0.78 | 300 | 302 | 25LG3-10×6 N=2.2kw | 2344 | P1=0.38 PS1=0.55 P2=0.52 PS2=0.60
 | 72 | 
| 13 | B | 0.38-0.50 | SQL1000×1.0 | 0.78 | 300 | 302 | 25LG3-10×8 N=2.2kw | 2494 | P1=0.50 PS1=0.70 P2=0.67 PS2=0.75
 | 61 | 
| 14 | C | 0.50-0.65 | SQL1000×1.5 | 0.78 | 300 | 302 | 25LG3-10×10 N=3.0kw | 2689 | P1=0.65 PS1=0.88 P2=0.86 PS2=0.93
 | 51 | 
| 15 | D | 0.65-0.85 | SQL1200×1.5 | 0.85 | 300 | 355 | 25LG3-10×13 N=4.0kw | 2703 | P1=0.85 PS1=1.05 P2=1.02 PS2=1.10
 | 82 | 
| 16 | E | 0.85-1.00 | SQL1200×1.5 | 0.85 | 300 | 355 | 25LG3-10×15 N=4.0kw | 2730 | P1=1.00 PS1=1.21 P2=1.19 PS2=1.26
 | 73 | 
| 17 | ZW(L)-II-XZ- | A | 0.22-0.38 | SQL1200×0.6 | 0.80 | 450 | 474 | 25LG3-10×6 N=2.2kw | 3641 | P1=0.38 PS1=0.53 P2=0.50 PS2=0.58
 | 133 | 
| 18 | B | 0.38-0.50 | SQL1200×1.0 | 0.80 | 450 | 474 | 25LG3-10×8 N=2.2kw | 3947 | P1=0.50 PS1=0.68 P2=0.65 PS2=0.73
 | 110 | 
| 19 | C | 0.50-0.65 | SQL1200×1.5 | 0.80 | 450 | 474 | 25LG3-10×10 N=3.0kw | 3961 | P1=0.65 PS1=0.87 P2=0.84 PS2=0.92
 | 90 | 
| 20 | D | 0.65-0.85 | SQL1200×1.5 | 0.80 | 450 | 474 | 25LG3-10×12 N=4.0kw | 4124 | P1=0.85 PS1=1.12 P2=1.09 PS2=1.17
 | 73 | 
| 21 | E | 0.85-1.00 | SQL1200×1.5 | 0.80 | 450 | 474 | 25LG3-10×14 N=4.0kw | 4156 | P1=1.00 PS1=1.30 P2=1.27 PS2=1.35
 | 64 | 
| 注:1、表中运行压力符号:P1—气压水罐的充气压力(消防需要的压力)(MPa)。 P2—消防泵启动压力(MPa)。
 Ps1—增压稳压水泵启动压力(MPa)。
 Ps2—增压稳压水泵停泵压力(MPa)。
 2、表中序号1-6为Ⅰ型“设备”,一般设在高位水箱间(最不利点消火栓低于“设备”)。
 3、表中序号7-21为Ⅱ型,“设备”一般设在消防泵房、储水池间,其消防压力范围,配用水泵等仅供选用参考。
 4、表中水泵型号为本公司的水泵型号,根据流量、扬程可改选项其他水泵。
 |